Fixed and portable refrigerant gas detection for marine refrigeration and air-conditioning plant. ANP surveys, designs, supplies, installs, calibrates and maintains detection systems that warn the crew, trigger ventilation and keep your vessel compliant with EN 378 and F-Gas requirements — supported by 24/7 worldwide attendance.
Detection, alarm and ventilation interlock for refrigerating machinery rooms.
Detection and records that underpin leak-check and CO₂e compliance.
Emergency attendance and resupply for vessels worldwide.
Gas calibration with certificates for class and flag-state inspection.
A refrigerant leak in an enclosed machinery space is a safety, compliance and commercial risk at once. Fixed detection gives the earliest possible warning so the crew can act.
Refrigerant leaks can displace oxygen or release toxic, flammable vapour in enclosed machinery spaces. Early detection protects the crew before concentrations become dangerous.
EN 378 and the F-Gas regime require fixed detection, alarms and ventilation interlocks in refrigerating machinery rooms. Detection underpins your leak-check records and class surveys.
HFCs and blends carry high global-warming potential. Catching leaks early cuts emissions, refrigerant loss and the cost of top-up gas.
An undetected leak means lost charge, poor performance and provision-plant or AC failure at sea. Detection avoids spoiled cargo, breakdowns and emergency call-outs.
A marine refrigerant detection system links gas sensors to a controller that drives alarms and ventilation, and logs every event for your records.
Fixed transmitters sense refrigerant at ppm level near likely leak points.
A panel continuously monitors every sensor and compares to alarm set-points.
Audible and visible alarms warn the crew the moment a threshold is crossed.
The controller interlocks emergency mechanical ventilation to clear the space.
Events and tests are recorded to support F-Gas logs and surveys.
Different refrigerants and duties call for different sensing technologies. We specify the right sensor for the gas, the space and the alarm strategy.
| Technology | Best suited to | Detection | Strengths | Typical life |
|---|---|---|---|---|
| Electrochemical | Toxic gases — ammonia (R-717) | Low ppm | Target-specific, very low detection threshold, stable at low concentrations | 3–5 years |
| Semiconductor (MOS) | Broad HFC/HC coverage, general alarm | ppm | Robust, low cost, fast, wide gas range | 5–7 years |
| Infrared (NDIR) | HFCs, blends & CO₂ (R-744) | ppm | Selective, drift-free, no false alarms from other gases, long life | 7–10 years |
| Ultrasonic | High-pressure leak location | Leak rate | Hears the leak rather than the gas — instant, gas-independent | 8–10 years |
| Heated diode | Portable service & pinpointing | g/yr | Hand-held sensitivity for locating the exact leak point | 1–2 years (tip) |
Detection thresholds, sensor placement and ventilation set-points are engineered case by case to EN 378 and the relevant standards, and depend on the refrigerant, charge size, room volume and the vessel's flag state. Figures shown are indicative — confirm against current regulations at design stage.
From common HFC blends to CO₂ and ammonia, each refrigerant has its own hazard profile and recommended sensing approach.
ANP delivers the whole lifecycle of marine refrigerant detection — one engineering partner from first survey to ongoing calibration.
We assess each machinery space, refrigerant type and charge, room volume and ventilation against EN 378 to define what detection is required.
Sensor selection and placement, alarm strategy, ventilation interlock and panel specification — engineered to the gas and the space.
Fixed detectors, controllers, beacons/sounders and portable instruments from established marine-approved manufacturers.
Fitting, wiring, interlock to ventilation, function testing and alarm verification — alongside or during refit.
Gas calibration with certificates for class and flag-state inspection, plus documented test records.
Scheduled calibration, bump-testing and sensor replacement, backed by 24/7 worldwide attendance.
Common questions from technical superintendents and fleet managers on marine refrigerant gas detection.
Where a refrigerating system sits in a dedicated machinery room, EN 378 requires a fixed detector that triggers an alarm and emergency mechanical ventilation. The F-Gas regime separately requires automatic leak detection on larger charges and periodic leak checks scaled to the system's CO₂-equivalent charge. Exact duties depend on the refrigerant, charge size and the vessel's flag state.
Sensor placement follows the density of the gas — low down for heavier-than-air refrigerants such as most HFCs and CO₂, higher up for lighter gases such as ammonia — and close to the most likely leak sources around the compressor, receiver and joints. We confirm positions during survey.
Sensors drift over time, so calibration and bump-testing on a planned schedule is essential to keep alarms accurate. We provide calibration with certificates suitable for class and flag-state inspection, and manage sensor replacement at end of life.
Yes. We survey the existing system and machinery space, then design and install detection, alarms and ventilation interlocks that suit the refrigerant and room — typically scheduled alongside planned maintenance or refit.
Tell us your vessel, refrigerant and machinery spaces and we'll scope a compliant detection system — survey, design, supply, install and maintain, worldwide.
Request a Survey24/7 emergency refrigeration engineering and detection support for vessels worldwide.